10_EnOcean: EEP changed: contact (EEP D5-00-01), lightTempOccupSensor.01 (EEP A5-08-01): modified for Eltako sensors TK-BHSB, TF-FKB

git-svn-id: https://svn.fhem.de/fhem/trunk@19820 2b470e98-0d58-463d-a4d8-8e2adae1ed80
This commit is contained in:
klaus.schauer 2019-07-12 17:36:23 +00:00
parent 6450c9c796
commit 90df134fbd

View File

@ -9765,10 +9765,16 @@ sub EnOcean_Parse($$)
if ($st eq "lightTempOccupSensor.01") { if ($st eq "lightTempOccupSensor.01") {
# Light, Temperatur and Occupancy Sensor (EEP A5-08-01) # Light, Temperatur and Occupancy Sensor (EEP A5-08-01)
# [Eltako FABH63, FBH55, FBH63, FIBH63] # [Eltako FABH63, FBH55, FBH63, FIBH63, TF-BHSB]
if ($manufID eq "00D") { if ($manufID eq "00D") {
if ( $model eq 'Eltako_TF') {
$lux = $db[2] << 1;
push @event, "3:state:M: $motion E: $lux U: $voltage";
push @event, "3:voltage:$voltage";
} else {
$lux = sprintf "%d", $db[2] * 2048 / 255; $lux = sprintf "%d", $db[2] * 2048 / 255;
push @event, "3:state:M: $motion E: $lux"; push @event, "3:state:M: $motion E: $lux";
}
} else { } else {
$lux = $db[2] << 1; $lux = $db[2] << 1;
$temp = sprintf "%0.1f", $db[1] * 0.2; $temp = sprintf "%0.1f", $db[1] * 0.2;
@ -10649,6 +10655,11 @@ sub EnOcean_Parse($$)
push @event, "3:state:Manufacturer Specific Application unknown"; push @event, "3:state:Manufacturer Specific Application unknown";
} }
} elsif ($st eq "contact" && $manufID eq "00D") {
# Eltako TF-FKB voltage telegram
push @event, "3:voltage:" . sprintf "%0.1f", $db[2] * 0.02;
push @event, "3:energyStorage:" . sprintf "%0.1f", $db[3] * 0.02;
} elsif ($st eq "PM101") { } elsif ($st eq "PM101") {
# Light and Presence Sensor [Omnio Ratio eagle-PM101] # Light and Presence Sensor [Omnio Ratio eagle-PM101]
# The sensor also sends switching commands (RORG F6) with the senderID-1 # The sensor also sends switching commands (RORG F6) with the senderID-1
@ -18115,7 +18126,8 @@ EnOcean_Delete($$)
The attr subType must be contact. The attribute must be set manually. The attr subType must be contact. The attribute must be set manually.
A monitoring period can be set for signOfLife telegrams of the sensor, see A monitoring period can be set for signOfLife telegrams of the sensor, see
<a href="#EnOcean_signOfLife">signOfLife</a> and <a href="#EnOcean_signOfLifeInterval">signOfLifeInterval</a>. <a href="#EnOcean_signOfLife">signOfLife</a> and <a href="#EnOcean_signOfLifeInterval">signOfLifeInterval</a>.
Default is "off" and an interval of 1980 sec. Default is "off" and an interval of 1980 sec.<br>
Set the manufID to 00D for Eltako devices that send a periodic voltage telegram. (For example TF-FKB)
</li><br><br> </li><br><br>
<li>Room Sensor and Control Unit (EEP A5-10-02)<br> <li>Room Sensor and Control Unit (EEP A5-10-02)<br>
@ -20432,17 +20444,19 @@ EnOcean_Delete($$)
<li>Single Input Contact, Door/Window Contact<br> <li>Single Input Contact, Door/Window Contact<br>
1BS Telegram (EEP D5-00-01)<br> 1BS Telegram (EEP D5-00-01)<br>
[EnOcean EMCS, STM 320, STM 329, STM 250, Eltako FTK, Peha D 450 FU] [EnOcean EMCS, STM 320, STM 329, STM 250, Eltako FTK, Peha D 450 FU, Eltako TK-TKB]
<ul> <ul>
<li>closed</li> <li>closed</li>
<li>open</li> <li>open</li>
<li>alarm: dead_sensor</li> <li>alarm: dead_sensor</li>
<li>battery: U/V (Range: U = 0 V ... 5 V</li>
<li>energyStorage: U/V (Range: U = 0 V ... 5 V</li>
<li>teach: &lt;result of teach procedure&gt;</li> <li>teach: &lt;result of teach procedure&gt;</li>
<li>state: open|closed</li> <li>state: open|closed</li>
</ul></li> </ul></li>
The device should be created by autocreate. A monitoring period can be set for signOfLife telegrams of the sensor, see The device should be created by autocreate. A monitoring period can be set for signOfLife telegrams of the sensor, see
<a href="#EnOcean_signOfLife">signOfLife</a> and <a href="#EnOcean_signOfLifeInterval">signOfLifeInterval</a>. <a href="#EnOcean_signOfLife">signOfLife</a> and <a href="#EnOcean_signOfLifeInterval">signOfLifeInterval</a>.
Default is "off" and an interval of 1310 sec. Default is "off" and an interval of 1980 sec.
<br><br> <br><br>
<li>Temperature Sensors with with different ranges (EEP A5-02-01 ... A5-02-30)<br> <li>Temperature Sensors with with different ranges (EEP A5-02-01 ... A5-02-30)<br>
@ -20642,7 +20656,7 @@ EnOcean_Delete($$)
Eltako and PEHA devices only support Brightness and Motion.<br> Eltako and PEHA devices only support Brightness and Motion.<br>
The attr subType must be lightTempOccupSensor.<01|02|03> and attr The attr subType must be lightTempOccupSensor.<01|02|03> and attr
manufID must be 00D for Eltako Devices. This is done if the device was manufID must be 00D for Eltako Devices. This is done if the device was
created by autocreate. created by autocreate. Set model to Eltako_TF manually for Eltako TF Devices.
</li> </li>